Three Phase Single Phase Voltage Regulator

Customizable

The SBW and DBW series AC compensated voltage regulators (hereinafter referred to as voltage regulators) are power supply products independently researched and developed by our company in response to the current situation of China’s national power grid. 

SBW/DBW Series AC Compensated Voltage Regulator
Product Overview

The SBW and DBW series AC compensated voltage regulators (hereinafter referred to as voltage regulators) are power supply products independently researched and developed by our company in response to the current situation of China's national power grid. They can automatically maintain a stable output voltage when external power supply network voltage fluctuations or load changes cause voltage variations. Compared with other types of voltage regulators, this series of products has the advantages of large capacity, high efficiency, no waveform distortion, and stable voltage regulation. They are suitable for a wide range of loads, can withstand instantaneous overload, can work continuously for long periods, support manual/automatic switching, and are equipped with overvoltage protection, phase loss, phase sequence protection, and automatic mechanical fault protection. The machines are reliable in operation, compact in size, lightweight, and convenient to use and install. This series of products has passed the European Union 'CE' certification and obtained authoritative testing from the Shanghai Testing Center certification authority, and can be used interchangeably with foreign products.

Core Advantage
  • High voltage regulation accuracy: Uses an RMS true value sampling control board, with adjustable voltage regulation accuracy from 1% to 5%.
  • Fast adjustment speed: Machine tool slide conduction technology, response time ≤ 0.04s, stabilization time <1.2s.
  • Comprehensive protection features: Equipped with overvoltage, undervoltage, overcurrent, short circuit, overheat, phase loss, and other protection functions.
  • Wide voltage regulation range: Standard ±15%, customizable range ±20%~±50%.
  • High overall efficiency: Regulator efficiency ≥ 98%.
  • Stable control technology: Advanced MCU measurement control, imported metering chip design technology, system precise and stable.
  • Excellent output waveform: Output voltage waveform distortion-free, no harmonics.
  • High-quality materials: 0.35mm high magnetic conductivity, low-loss coated silicon steel sheets, C1017 alloy brushes.
  • High degree of automation: System fully automatic voltage regulation, delayed start, fault recovery automatic restoration functions.
  • Large load capacity: Regulator capacity selectable from 1kVA to 3600kVA.
  • Wide load compatibility: Suitable for any load.
  • Comprehensive communication functions: RS485/RS232/GPRS optional.
Capacity range Three-phase capacity SBW-20-3600kVA; Single-phase capacity: DBW-10-500kVA
Input voltage Three-phase 380Vac ±15%; Three-phase 380Vac ±20%; Customizable ±20% ±50%
Output voltage Three-phase 380Vac Single-phase 220Vac; Output voltage can be customized according to customer requirements, such as 200V, 208V, 400V
Voltage regulation accuracy 1%-5% adjustable
Frequency range 50Hz/60Hz
Efficiency 98%(for power ratings of 50kVA and above)
Response speed ≤ 0.04S
Stabilization speed When the input voltage steps change by 10% relative to the rated value, the stabilization time ≤ 1.2S
Insulation resistance ≥ 2MΩ
Insulation strength 2000V withstand for 1 minute without breakdown
Waveform distortion Compared to the input voltage waveform, the relative harmonic content increase of the output voltage waveform does not exceed 1%
Communication function Optional RS232, RS485, GPRS interfaces to achieve remote signaling, remote measurement, and remote control functions
Display function High-brightness LCD display, capable of showing input and output voltage, output current, frequency, temperature, and fault alarm status. HMI touch screen display (optional)
Protection function Features delayed output, alarms and protection for overvoltage, undervoltage, overload, short circuit, overheat, phase loss, reverse phase, etc., and can automatically resume stable power supply after a fault is cleared.
Operating temperature -15℃-+45℃
Relative humidity 10%-90%(20℃ ±5℃)
Altitude <1000m; for altitudes exceeding the standard, the de-rating should follow GB1094.11.2013 'Dry-type Transformer', Article 11.3
Protection level IP21, customizable protection level below IP56
Noise < 60dB
Standards YD/T1074-2000 'Communication AC Voltage Regulator'; JB/T7620-1994 'Compensation-type AC Voltage Regulator'