GCK

Customizable

The GCK low-voltage withdrawable switchgear complete switchgear equipment is suitable for low-voltage distribution systems with AC 50Hz and a rated operating voltage of 380V. It includes the functions of Power Center (PC) and Motor Control Center (MCC).

Product Overview

The GCK low-voltage withdrawable switchgear complete switchgear equipment is suitable for low-voltage distribution systems with AC 50Hz and a rated operating voltage of 380V. It includes the functions of Power Center (PC) and Motor Control Center (MCC). All technical parameters meet national standards, featuring a complete structure, attractive appearance, high electrical performance, high protection level, safety and reliability, and easy maintenance. It is an ideal distribution device for low-voltage power supply systems in industries such as metallurgy, petroleum, chemical, electric power, machinery, and light textile industries. This product complies with IEC-439 and GB7251.1 standards.

Core Advantage
  • GCK1 and GCJ1 have a modular assembly structure, with the basic frame made of special profiles, assembled together.
  • The cabinet frame, component dimensions, and opening sizes change according to the basic module E=25mm.
  • In the MCC scheme, the cabinet is divided into five areas (compartments): horizontal busbar area, vertical busbar area, functional unit area, cable compartment, and neutral grounding busbar area. Each area is isolated from the others to ensure normal circuit operation and effectively prevent the spread of faults.
  • Since all structures of the frame are fastened together with screws, welding deformation and stress are avoided, improving precision.
  • Components are highly interchangeable, widely applicable, and highly standardized.
  • The functional units (drawers) are operated with a lever for pulling out and inserting, and with rolling bearings, the operation is easy and reliable.
Technical Specifications
Parameter Value
Protection levelIP40、IP30
Rated working voltageAC、380(V)
Frequency50Hz
Rated insulation voltage660V
Working conditions
  Environment室内 Indoors
  Altitude≤ 2000m
  Ambient temperature-5℃ ~ +40℃
  The min temperature under store and transportation-30℃
  Relative humidity≤ 90%
(kW)Capacity of control motor(kW)0.4~155
(A) Rated Current & Bus Bar Parameters
Item Parameter Value
Horizontal bus bar1600、2000、3150
Vertical bus bar630、800
Contact connector of main circuit200、400
Feeding circuit1600
Max currentCabinet630
Cabinet1000、1600、2000、2500、3150
Power receiving circuitCabinet
(kA) Rated short time withstand current(kA)
  Virtual value50、80
  Peak value105、176
(V/1min) Line frequency withstand voltage(V/1min)2500
Outline Dimensions Diagram
GCK Drawer Cabinet Structure Diagram

GET IN TOUCH