General Purpose Armored Withdrawable Switchgear

Customizable

The KYN28-24(Z) series armored withdrawable AC metal-enclosed switchgear (hereinafter referred to as “switchgear”) is a complete set of distribution equipment for 20kV three-phase AC 50(60)Hz single busbar and single busbar sectional systems.

Product Overview

The KYN28-24(Z) series armored withdrawable AC metal-enclosed switchgear (hereinafter referred to as "switchgear") is a complete set of distribution equipment for 20kV three-phase AC 50(60)Hz single busbar and single busbar sectional systems. It is mainly used in power plants, medium and small generator power supply, distribution for industrial and mining enterprises, and secondary substations in power systems for receiving and transmitting electricity, as well as starting large high-voltage motors. It is used for control, protection, and monitoring. This switchgear has the "five-proof" interlocking functions, which prevent the withdrawal of the circuit breaker under load, prevent mistaken opening or closing of the circuit breaker, prevent closing the circuit breaker when the grounding switch is in the closed position, prevent entering live compartments by mistake, and prevent faulty closing of the grounding switch when energized. It can be equipped with the VS1-24 type vacuum circuit breaker developed and trial-manufactured by our company, making it an excellent performance distribution device. The product complies with standards such as GB 3906, GB/T 11022, and IEC 60298.

Technical Parameters

Name Unit Value (Matched circuit breaker VS1-24)
Rated voltagekV24
1min power frequency withstand voltagekV(50)65
Rated impulse withstand voltage (peak)kV125
Rated frequencyHz50(60)
Rated currentA630, 1250, 1600, 2000, 2500, 3150
Rated current of branch busbarA630, 1250, 1600, 2000, 2500
Rated short-time withstand currentkA16, 20, 25, 31.5
Rated peak withstand currentkA40, 50, 63, 80
Rated short-circuit durations4
Protection levelThe enclosure is IP4X, it is IP2X when the compartment door and circuit breaker chamber door are opened
Masskg800, 1000 (Rated current above 1600A)

Structure Diagram

Components
1Wall bushing
2Analog primary diagram
3Nameplate
4Illuminating lamp
5Main busbar
6Contact box
7Current transformer
8Primary cable
9Earthing busbar
10Secondary interlocking assembly
11Valve mechanism
12Handcart of circuit breaker
13Insulator
14Heater
15Framework of cabinet body
KYN28-24 Structure Diagram

GET IN TOUCH

We are happy to help you.