12KV Box Type Fixed SF6 Ring Main Unit

Customizable

The XGN15-12 box-type fixed AC metal-enclosed switchgear (hereinafter referred to as the ring main unit) is a new type of high-voltage electrical product that we have independently designed and developed by introducing excellent foreign technology and in accordance with the requirements of domestic rural power and urban network renovation.

Product Overview

The XGN15-12 box-type fixed AC metal-enclosed switchgear (hereinafter referred to as the ring main unit) is a new type of high-voltage electrical product that we have independently designed and developed by introducing excellent foreign technology and in accordance with the requirements of domestic rural power and urban network renovation. All technical performance indicators fully comply with IEC62271-200:2003 and GB3906 standards.

The main switch, operating mechanism, and components of the ring main unit use original ABB parts or SFL-12/24 type switchgear assembled domestically with imported components. Additionally, it can be equipped with original ABB HAD/US SF6 circuit breakers or vacuum circuit breakers according to user requirements. The operation modes include manual and motorized operation.

The cabinet is processed by CNC machines and then riveted, achieving a protection level of IP3X, and features reliable mechanical interlocks and anti-misoperation functions. This product is characterized by its compact size, light weight, attractive appearance, ease of operation, long service life, high parameters, environmental friendliness, and low maintenance requirements.

The XGN15-12 box-type fixed AC metal-enclosed switchgear is suitable for use in 50Hz, 12kV power networks, serving as equipment for receiving and distributing electrical energy. The main switch inside the cabinet is an SF6 switch.

Technical Parameters

No. Name Unit Numerical value
1Rated voltagekV12
2Rated frequencyHz50
3Rated current of main bus / maximum rated current of fuseA630, 125
4Rated short-time withstand current of main circuit and grounding circuitkA/s20, 3
5Rated peak withstand current of main circuit and grounding circuitkA50
6Rated short-circuit making current of main circuit and grounding circuitkA50
7Breaking number of load switch at full capacityTime100
8Fuse breaking currentkA31.5, 40
9Rated closed-loop breaking currentA630
10Rated transfer currentA1600
11Mechanical lifeTime2000
121 min power frequency withstand voltage (peak) relative, ground / isolation fracturekV42, 48
13Lightning impulse withstand voltage (peak) interphase, ground / isolation breakkV75, 85
141min power frequency withstand voltage of secondary circuitkV2
15Protection gradeIP3X
No. Name Unit Numerical value
1Width of circuit breaker cabinetmm750
2Other cabinet widthmm375, 500
3Highmm1600, 1850
4Deepmm980, 900
5Relay box highmm450

Structure Diagram

XGN15-12 Structure Diagram

GET IN TOUCH