12KV Armored Withdrawable Switchgear

Customizable

This device is an indoor metal-clad withdrawable switchgear (hereinafter referred to as switchgear), designed for 3.6-12 kV three-phase AC 50Hz single busbar and single busbar sectional systems.

Product Overview

This device is an indoor metal-clad withdrawable switchgear (hereinafter referred to as switchgear), designed for 3.6-12 kV three-phase AC 50Hz single busbar and single busbar sectional systems. It is a complete set of distribution equipment mainly used in power plants, for the power supply of small and medium-sized generators, distribution for industrial and mining enterprises, reception and supply in secondary substations of power systems, as well as starting of large high-voltage motors. It implements control, protection, and monitoring functions. This switchgear meets the requirements of standards such as IEC298 and GB3906, featuring interlock functions that prevent the withdrawal of the circuit breaker under load, prevent incorrect opening or closing of the circuit breaker, prevent closing the circuit breaker when the grounding switch is in the closed position, prevent accidental entry into live compartments, and prevent incorrect operation of the grounding switch while energized. It can be equipped with either the VS1 vacuum circuit breaker or ABB's VD4 vacuum circuit breaker, making it a highly efficient and superior distribution device.

Technical Parameters

Name Unit ZN63A-12(VS1) VD4
Rated voltagekV1212
1min power frequency endurable voltagekV4242
Rated impulse withstand voltage (peak value)kV7575
Rated frequencyHz5050
Rated currentA630, 1250, 1600, 2000, 2500, 3150, 4000, 5000630, 1250, 1600, 2000, 2500, 3150, 4000, 5000
Rated current of branch busbarA630, 1250, 1600, 2000, 2500, 3150, 4000, 5000630, 1250, 1600, 2000, 2500, 3150, 4000, 5000
Rated short time withstand current (virtual value)kA16, 20, 25, 31.5, 40, 5016, 20, 25, 31.5, 40, 50
Rated peak endurable voltagekA40, 50, 63, 80, 100, 12540, 50, 63, 80, 100, 125
Rated short-circuit durations44
Protection levelThe shell is IP4X, and IP2X when compartment door and handcart door are opened
Weightkg700~1200700~1200

Structure Diagram

Rooms
Athe bus bar room
Bthe circuit breaker handcart room
Cthe cable room
Dthe relay instrument room
Components
1cover
2branch small bus bar
3bus bushing
4main bus bar
5statie contact device
6contact box
7current mutual induction current transfor
8earthed switch
9cable
10arrester
11earthed main bus bar
12mother board
13control the small bus bar
14earthed switch operating mechanism
15draw-out horizontal clapboard
16heafing device
17circuit breaker handcart
18scondary plug
19clapboard(valve)
20loading and unloading clapboard
21pressure release channel
KYN28-12 Structure Diagram

GET IN TOUCH

We are happy to help you.