Metal Clad Fully Enclosed SF6 Ring Main Unit

Customizable

Metal fully enclosed gas-insulated ring main unit is an SF6 gas-insulated metal enclosed switchgear. This equipment can be composed of modules such as load switch units, load switch-fuse combination units, vacuum circuit breakerunits, and busbar inlet units.

Product Overview

Metal fully enclosed gas-insulated ring main unit is an SF6 gas-insulated metal-enclosed switchgear. This equipment can be composed of modules such as load switch units, load switch-fuse combination units, vacuum circuit breaker units, and busbar inlet units. It incorporates a series of advanced technologies and materials, offering excellent electrical and mechanical performance, minimal impact from environmental and climatic conditions, compact size, easy installation, convenient operation, and maintenance-free use, as well as flexible combination options. Its clear and intuitive design ensures simple and straightforward operation. The feeder connection capacity is large, making it suitable for various wiring systems.

Core Advantage

Technical Description

The gas-insulated high-voltage AC metal-enclosed switchgear is installed on a galvanized sheet frame. The switch units are housed within SF6 gas compartments, which are made of 3mm thick corrosion-resistant and non-magnetic stainless steel plates. The SF6 gas compartment is a "sealed pressure system" that can operate for 30 years under normal working conditions. The normal operating pressure of SF6 gas is 0.15~0.4 bar. The gas compartment is equipped with a pressure relief device to ensure that gas can be released from the bottom or the rear when the pressure is too high.

Switch Unit

The load switch adopts a coaxial rotating double-break design, which operates through the same operating hole in conjunction with a sliding plate, so the switch can only be in one of three states at any time: "closed, open, or grounded," completely preventing misoperation.

Operating Mechanism

The switch operating mechanism is installed at the front outside of the gas compartment, treated with special processes for rust prevention, which facilitates manual operation and maintenance, and can also easily be integrated for electric operation.

Technical Parameters

Project Unit C module load switch unit F module load switch-fuse combination electric unit V module breaker unit
Rated voltagekV121212
Rated currentA630125 Note(1)630
Power frequency withstand voltage / 1 minutekVPhase/phase424242
Fracture484848
Impact pressurekVPhase/phase75-75
Fracture85-85
Rated closed-loop breaking currentA630--
Rated cable charging breaking currentA30--
Rated breaking inductive currentANote(2)--
Rated short-time withstand current /3skA20-20
Rated peak withstand currentkA50170050
Rated transfer currentA-Note(3)-
Rated short-circuit breaking currentkA--20
Rated short-circuit currentkA50--
Rated short circuit breaking frequencytimes--30
Rated short circuit closing times
(load switch/grounding switch)
times5/5--
Rated current breaking frequencytimes>100--
Number of mechanical operations
(load switch/grounding switch)
times5000/20005000/200030000
Note: 1.Depending on the rated current of the fuse;
2.Open breaking 1250kVA no-load transformer;
3.Depending on high-voltage fuses;